COMPUTER ROOM applications include systems to serve critical computer room equipment as well as telecommunication rooms and other areas requiring precise temperature and humidity control.


DESIGN, INSTALLATION and SERVICE
CONVERSION / RETROFIT
SYSTEMS ANALYSIS and EVALUATION




CRITICAL APPLICATIONS

> Computer Rooms
> Clean Rooms
> Laboratory Applications
> Telecommunication Rooms
> MCC Rooms
> Control Centers

As a full service contractor our in-house staff can provide design, installation and service for all types of systems. We can help with applications engineering for new construction or renovations as well as energy analysis to help with return on investment analysis.





Computer Room Unit Sample Projects

COMPUTER ROOM UNITS FOR NEWSPAPER PRODUCTION PLANT
Installed two computer room units to provide 6,400 CFM of supply air for temperature and humidity control to the computer controlled press equipment in the main production plant. The units include reheat for humidity control, a steam generator humidifier, microprocessor controller with LCD display, low ambient head pressure controls, dual independent refrigeration controls and smoke detector.

I/O & COMPUTER ROOM UNITS PETROLEUM REFINERY
To control building pressurization, cooling and dehumidification for one of the most critical switch gear rooms in the refinery we installed two computer room units. A single unit was replaced with these two 10-ton multistage units. Each is staged in 5-ton increments allowing for 100% redundancy and set up as lead/lag units to balance the run time on each. Controls were modified to run both supply fans and ductwork extended from the existing scrubber for the new unit and air is diverted to provide pressurization to the I/O and Computer Room. We installed a 200-amp Westinghouse MLO panel board feed from a 200-amp breaker and all condenser disconnects are rated for a Class 1 Division 2 location. Demo of the existing unit and installation of the new units was staggered to eliminate downtime to the building.

MANUFACTURING PLANT CLEAN ROOMS
Designed and installed two units to condition a class 10,000 Clean Room and a Large Workroom area maintaining a positive pressure in these areas in relation to the adjacent production areas. The Clean Room included adding eight fan powered HEPA ceiling mounted supply grilles, all needed return air sidewall registers, all sealed and insulated supply and return air ductwork and complete air balance of the system. The Large Workroom was not intended to meet a class 100,000 clean room design but included lowering the supply air ductwork to hang two feet above the finished ceiling, all lay in ceiling grilles and five low sidewall return air grilles. Each grille was ducted above the wall of the room and return air mixes with plant air and is then drawn back to the unit.